Shanghai Mitsubishi GPS-II/GPS-III/HOPE/LEHY-C Load Weighing Calibration Manual

Mitsubishi voltage calibration cross-model adjustment load compensation algorithm Mitsubishi HOPE calibration oil cup alignment MON potentiator Mitsubishi multi-model voltage calibration

FELEVATOR2 min read
Read the article
Shanghai Mitsubishi GPS-II/GPS-III/HOPE/LEHY-C Load Weighing Calibration Manual
The FELEVATOR journal

I. GPS/HOPE Series Specific Calibration

1. No-Load Calibration

  1. Position elevator at mid-floor (oil cup alignment)

  2. Set MON(MON0) potentiometer to "2"

  3. Adjust differential transformer spring until P1 boArd displays "65-70" (Ensure cabin empty)

  4. Toggle LD0/LD1 switch to LD0 → Data saved when display stabilizes


2. Half-Load Calibration

  1. Position elevator at mid-floor

  2. Set MON(MON1) potentiometer to "2"

  3. Manually pull weighing plate to achieve "≈114" (Displayed as "14.")

  4. Toggle LD0/LD1 switch to LD1 → Data saved when display stabilizes


3. Compensation Writing

  1. Position empty cabin at bottom floor

  2. Toggle FMS switch in high-speed mode → P1 display blinks

  3. Immediately toggle DCB switch → Elevator ascends at 1m/s

  4. Repeat ≥3 cycles (30-second intervals recommended)


II. LEHY-C Series Specific Calibration

1. No-Load Calibration (Voltage Reference)

  1. Position elevator at mid-shaft

  2. Machine Room Operation:

    • Adjust "ZERO" potentiometer to achieve 0.5V±0.02V between OUT+/-

  3. Control Panel Operation:

    • Set SET1=6, SET0=2

    • Single SW1 toggle → Data saved when 7-segment stops blinking


2. Half-Load Calibration

  1. Position elevator at mid-shaft with 50% load

  2. Machine Room Operation:

    • Adjust "OUTPUT" potentiometer to 2.5V±0.05V

  3. Control Panel Operation:

    • Set SET1=6, SET0=3

    • Single SW1 toggle → Data saved


3. Compensation Writing

  1. Position empty cabin at bottom

  2. Set SET1=0, SET0=7

  3. Single SW1 toggle → Auto-ascend to top

  4. Repeat 3 cycles (Compensation accumulates)


III. System Functions

Cross-Model Functions

Function LEHY-C Operation GPS/HOPE Series
Disable SET1=4+SET0=0 double toggle WGHO to "0"
Load% MON1=3+MON0=6+SW1 MON(MON0)="C"
Read No-Load MON0="D"+LD0 MON(MON0)=D+LD0

Safety regulations:

●CAT III 1000V grade test leads must be used for voltage measurement

●It is strictly forbidden to enter the shaft during the compensation operation (the elevator will run continuously)

Note: Execute ECD-25 self-test after LEHY-C sensor calibration.


Technical Resource: www.felevator.com

Working on a similar project?

Send a part number or photo. Our team can help with the next step.

Ask our team

Let’s get to work

Your next part.
One conversation away.

Send us a part number or photo. We’ll help you check the details, availability, and shipping options.

felevator@outlook.com

Part number · Model · Quantity · Destination

Image detail